 10W Single Output Industrial DIN Rail Power Supply
Features :
Universal AC input/Full range
MDR-10
series
Protections: Short circuit / Overload / Over voltage Cooling by free air convection Can be installed on DIN rail TS-35/7.5 or 15 NEC class 2 / LPS compliant Built in DC OK active signal LED indicator for power on No load power consumption<0.75W 100% full load burn-in test 3 years warranty
SPECIFICATION
MODEL DC VOLTAGE RATED CURRENT CURRENT RANGE RATED POWER OUTPUT VOLTAGE TOLERANCE Note.3 LINE REGULATION LOAD REGULATION SETUP, RISE TIME HOLD UP TIME (Typ.) VOLTAGE RANGE FREQUENCY RANGE INPUT EFFICIENCY (Typ.) AC CURRENT (Typ.) INRUSH CURRENT (Typ.) LEAKAGE CURRENT OVERLOAD PROTECTION OVER VOLTAGE FUNCTION MDR-10-5 5V 2A 0 ~ 2A 10W 5.0% 1.0% 5.0%
Note.5 500ms, 30ms/230VAC
MDR-10-12 12V 0.84A 0 ~ 0.84A 10W 120mVp-p 3.0% 1.0% 3.0% 1000ms, 30ms/115VAC at full load 25ms/115VAC at full load 120 ~ 370VDC 81%
MDR-10-15 15V 0.67A 0 ~ 0.67A 10W 120mVp-p 3.0% 1.0% 3.0%
MDR-10-24 24V 0.42A 0 ~ 0.42A 10W 150mVp-p 2.0% 1.0% 2.0%
RIPPLE & NOISE (max.) Note.2 80mVp-p
120ms/230VAC 85 ~ 264VAC 47 ~ 63Hz 77%
81%
84%
0.33A/115VAC 0.21A/230VAC COLD START 35A/115VAC 70A/230VAC <1mA / 240VAC Above 105% rated output power Protection type : Hiccup mode, recovers automatically after fault condition is removed 13.8 ~ 16.2V 17.25 ~ 20.25V 5.75 ~ 6.75V 11.5 ~ 16.5V / 40mA
27.6 ~ 32.4V 18 ~ 27V / 20mA
Protection type : Shut down o/p voltage, re-power on to recover 9 ~ 13.5V / 40mA DC OK ACTIVE SIGNAL (max.) 3.75 ~ 6V / 50mA WORKING TEMP. -20 ~ +70 (Refer to output load derating curve) 20 ~ 90% RH non-condensing -40 ~ +85 , 10 ~ 95% RH
WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS WITHSTAND VOLTAGE SAFETY & EMC
(Note 4)
0.03%/ (0 ~ 50 Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL508, TUV EN60950-1 approved, NEC class 2 / LPS compliant I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC ISOLATION RESISTANCE EMI CONDUCTION & RADIATION Compliance to EN55011,EN55022 (CISPR22), EN61204-3 Class B Compliance to EN61000-3-2,-3 HARMONIC CURRENT EMS IMMUNITY MTBF Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024,EN61000-6-1,EN61204-3, light industry level, criteria A 584K hrs min. MIL-HDBK-217F (25 22.5*90*100mm (W*H*D) 0.17Kg; 72pcs/13.2Kg/0.91CUFT )
OTHERS
NOTE
DIMENSION PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
File Name:MDR-10-SPEC 2008-06-07
10W Single Output Industrial DIN Rail Power Supply
Mechanical Specification
22.5
MDR-10
Case No. 956
100
series
Unit:mm
35
55
+V -V DC OK
DC OK
90
NL
Install DIN rail TS35/7.5 or TS35/15
55
Block Diagram
DC OK EMI FILTER RECTIFIERS & FILTER POWER SWITCHING RECTIFIERS & FILTER
fosc : 60KHz
DC OK +V -V
I/P
DETECTION CIRCUIT O.L.P. CONTROL O.V.P.
Application of DC OK Active Signal
(a) 5V signal
DC OK R Model 5V 12V 15V 24V R 200 1.5K 2K 3.9K
(b) LED
DC OK R Model 5V 12V 15V 24V R 1K 2.4K 3K 4.7K
(c) Relay
DC OK Model 5V 12V 15V 24V RL 120 700 700 1.2K
Relay
RL
5.1V V-
V-
V-
Derating Curve
100
Output Derating VS Input Voltage
Ta=25
100
Others
90 80
80
60
5V
70
LOAD (%)
LOAD (%)
0 10 20 30 40 50 60 70 (VERTICAL)
40
60 50 40
20
-20
85
95
100
115
120
140
160
180
200
220
240
264
AMBIENT TEMPERATURE ( )
INPUT VOLTAGE (VAC) 60Hz
File Name:MDR-10-SPEC 2008-06-07


▲Up To Search▲   

 
Price & Availability of MDR-10

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X